Reverse Osmosis

Brackish Water LP Series

Low Pressure

Efficient filtration at low pressure for cost-effective brackish water treatment.

Performance Specification

Operating data from the original catalog

Test pressure 150 psi (10.3 bar), NaCl concentration 2,000 ppm, recovery rate 15%, temperature 25°C, pH 7.

PropertyROMG 4040 LPROMG 8040 LP
Active Membrane7.9 m²41 m²
Average Permeate2,200 gpd (8.5 m³/d)10,500 gpd (38.4 m³/d)
Stable Rejection98.3%98.1%
Minimum Rejection97.9%97.7%
Spacer Mesh Thickness28 thou (0.72 mm)28 thou (0.72 mm)

Limits and Operating Conditions

ROMG 4040 LP

ParameterValue
Max. feed water flow rate16 gpm (3.6 m³/h)
Max. working pressure450 psi (31 bar)
Maximum Feedwater Temperature40°C
Feed water max. SDI15<3
pH range during continuous operation2~11
pH range during chemical cleaning2~12
Residual chlorine concentration<0.1 ppm
Max. pressure drop of a single element10 psi (0.07 MPa)
Max. Turbidity NTU1.0

Limits and Operating Conditions

ROMG 8040 LP

ParameterValue
Max. feed water flow rate70 gpm (16 m³/h)
Max. working pressure450 psi (31 bar)
Maximum Feedwater Temperature40°C
Feed water max. SDI15<3
pH range during continuous operation2~11
pH range during chemical cleaning2~12
Residual chlorine concentration<0.1 ppm
Max. pressure drop of a single element10 psi (0.07 MPa)
Max. Turbidity NTU1.0

Related in Reverse Osmosis